Case Study 4 - Elevator Control Problem
Environment
Newly constructed condominium building in Westchester County, NY.
Problem
The condominium developer could not get the necessary permits for operation because the
two building elevators would not run on the building's emergency back-up generator. The
problem was originally diagnosed as excessive voltage drop between the main service
entrance in the basement and the tenth floor motor room. The technicians involved spent a
lot of time and money trying to fix this presumed problem which had been incorrectly
diagnosed. Among the solutions tried were: Adjustment of the transformer taps to +5
percent, replacement of the transformer with a model with a lower impedance model, and
installation of an electronic tap switching regulator. A 450 kw emergency generator was
even brought in for testing to see if it would be necessary to replace the existing 175 kw
unit.
All of these attempts had some limited success, but none offered an acceptable
solution.
Measurements
A consultant used a power monitor to evaluate the quality of the voltage and current
supplied to the elevator motor. Figure 1 shows the current swell during motor
startup, while Figure 2 reveals the effect of the current demand on the voltage.

Figure 1. Current swell during motor startup.

Figure 2. Effect of motor startup current demand on voltage.
Solution
Using the power monitor was essential to uncover the real problem. Two factors became
evident: First, the true RMS voltage reported by the monitor showed that the values
measured by the less accurate average reading DVM's were misleading. The actual voltage
drop was not as severe as first indicated. Second, analysis of the current and voltage
waveforms (both visually and using harmonic analysis) showed that harmonic distortion, not
low voltage, was the real source of the problem, Figure 3.
The level of the fifth and seventh harmonics in the voltage waveform was due to the
reactance of the generator windings in response to nonlinear current demand from the
elevator motor controller. A circuit in the motor controller was sensitive to harmonic
distortion at these frequencies, mistaking them for a phase rotation error. The solution
was achieved by replacing this circuit at a cost of a few dollars.

Figure 3. Distorted voltage waveform exhibits relatively high fifth and seventh
harmonic content.
| Harmonic |
Percent Fundamental |
Phase Angle |
| Total |
19.2% |
|
| Odd |
18.7% |
|
| Even |
4.3% |
|
| 7th |
15.8% |
81 degrees |
| 5th |
9.8% |
268 degrees |
| 8th |
2.5% |
184 degrees |
| 2nd |
2.3% |
84 degrees |
This article brought to you
by: http://www.dranetz-bmi.com |